Technical data

This page lists the technical data for IOZER basic (IOZ-B-10).

Electrical data

Parameter Value
Supply voltage 7–30 V DC
Power consumption typ. < 5 W
Current consumption Depends on the configuration
Protection functions Reverse polarity protection, overvoltage protection, short-circuit protection

Interfaces

Interface Description
Ethernet 10/100 Mbit, RJ45
Wi-Fi IEEE 802.11 b/g/n, 2.4 GHz
RS485 Modbus RTU, IOZER link, optional 120-ohm bus termination using a jumper
1-Wire 1-Wire bus
Digital inputs 8 galvanically isolated inputs
Digital outputs 8 normally open outputs
USB USB-C service interface

Digital outputs

Parameter Value
Number 8 normally open (NO) contacts
Voltage max. 30 V DC
Current max. 300 mA per channel
Switching capacity max. 10 VA
Configuration Arranged in groups of four contacts with a shared common terminal (COM)
Status indication One LED per output

Digital inputs

Parameter Value
Number 8 galvanically isolated optocoupler inputs
Voltage max. 24 V DC
0 signal ≤ 2 V DC
1 signal ≥ 5 V DC
Undefined range > 2 to < 5 V DC
Configuration Arranged in groups of four inputs with a shared ground terminal (GND)
Status indication One LED per input

Wi-Fi

Parameter Value
Frequency band 2.4 GHz
Standard IEEE 802.11 b/g/n
Mode STA or AP
Security WPA2 / WPA3
Antenna Internal

Environment

Parameter Value
Degree of protection IP20, installation in enclosed operating locations
Operating temperature 0 °C to +50 °C
Storage temperature -20 °C to +70 °C
Humidity 10–90%, non-condensing

Mechanical data

Parameter Value
Installation Control cabinet / distribution board
Enclosure Industrial ABS plastic enclosure
Mounting 35 mm DIN rail according to EN 60715
Width 5 modular units
Flammability rating UL 94 HB
Device dimensions 90 × 79 × 50 mm (W × H × D)
Packaging dimensions 118 × 84 × 56 mm (W × H × D)
Device weight 120 g
Weight including packaging 155 g

Terminals

Parameter Value
Terminal type Pluggable screw terminals
Conductor cross-section 0.14–0.75 mm², AWG 26–18

Software functions

  • Local logic programming using Blockly and JavaScript
  • Event-based control using triggers and actions
  • Web interface for configuration and programming
  • MQTT client
  • Modbus RTU as master or slave
  • Modbus TCP as client or server
  • REST API
  • NTP time synchronization
  • Local data persistence

Firmware and updates

  • Secure OTA firmware updates
  • Firmware distribution through IOZER connect
  • Certificate-based device authentication
  • Manual firmware updates by file upload

Conformity

IOZER basic is designed for CE conformity, RED, and RoHS and complies with the following EMC and radio standards:

  • EN 301 489-1
  • EN 301 489-17
  • EN 300 328

Ordering information

Product Article number
IOZER basic IOZ-B-10

Scope of delivery

  • IOZER basic device
  • Quick guide
IOZER